- Product description
-
Product descriptionCombination arrester – type 1+2
• Plug-in arrester can be separated from base without tools and current cut-off in base
• Including thermal and dynamic cut-off unit and visual fault display
• High current conductivity and long service life
- Technical data
-
Connectivity options
Arrester surge current (8/20 µs) [total] 30 kA Blow-out no Conductor cross-section, rigid (single-wire/multiwire), max. 35 mm² Conductor cross-section, rigid (single-wire/multiwire), min. 2,5 mm² Dimension 150V Installation type On basic element Lightning protection zone LPZ 0→2 Lightning surge current (10/350 μs) 8 kA Lightning surge current (10/350) 8 kA Max. mains-side overcurrent protection 160 Maximum back-up fuse 160 A Maximum continuous voltage AC 150 V Maximum continuous voltage DC 200 V Maximum discharge current (8/20 μs) 50 kA Network form Other Nominal discharge current (8/20 µs) 30 kA Nominal voltage AC (50/60 Hz) 130 V Operating temperature, max. 80 °C Operating temperature, min. -40 °C Pole number 1 Pole version 1 Protection rating IP20 Remote signalling no Response time <25 ns Signalling on device Visual SPD to EN 61643-11 Type 1+2 SPD to IEC 61643-1 Class I+II Version for 1-pin cover; 150 V - All types
- Downloads
-
Data sheet V25-B+C 0-150 / 5097088 , 0.18MB , pdfCatalogue Überspannungsschutz , 28.42MB , pdfEU declaration of conformity V25-B+C 0-150 / 5097088 , 0.04MB , pdfREACH Declaration of conformity V25-B+C 0-150 / 5097088 , 0.12MB , pdfRoHS Declaration of conformity V25-B+C 0-150 / 5097088 , 0.12MB , pdfLabel approval EZU-Zertifikat V25 , 0.12MB , pdfSelection aid Selection aid, surge protection , 2.00MB , pdf
United Arab Emirates - English